
OPERATE
START
t
Timer
t
Level
detector
ENA_MULT
Directional
calculation
BLOCK
RCA_CTL
I
2
U
2
I3P
U3P
URES
Blocking
logic
IRES
Uo
DIRECTION
FAULT_DIR
Io
Figure 255: Functional module diagram
Level detector
The magnitude of the operating quantity is compared to the set
Start value and
the magnitude of the polarizing quantity is compared to the set
Voltage start value.
If both the limits are exceeded, the level detector sends an enabling signal to the
timer module. When the
Enable voltage limit setting is set to "False", Voltage start
value has no effect and the level detection is purely based on the operating quantity.
If the
ENA_MULT
input is active, the
Start value setting is multiplied by the Start
value Mult setting.
If the
Enable voltage limit setting is set to "True", the magnitude of the
polarizing quantity is checked even if the
Directional mode was set to
"Non-directional" or
Allow Non Dir to "True". The protection relay does
not accept the
Start value or Start value Mult setting if the product of
these settings exceeds the
Start value setting range.
Typically, the
ENA_MULT
input is connected to the inrush detection function
INRHPAR. In case of inrush, INRPHAR activates the
ENA_MULT
input, which multiplies
Start value by the Start value Mult setting.
Directional calculation
The directional calculation module monitors the angle between the polarizing
quantity and operating quantity. Depending on the
Pol quantity setting, the
polarizing quantity can be the residual voltage (measured or calculated) or the
negative sequence voltage. When the angle is in the operation sector, the module
sends the enabling signal to the timer module.
The minimum signal level which allows the directional operation can be set with the
Min operate current and Min operate voltage settings.
If
Pol quantity is set to "Zero. seq. volt", the residual current and residual voltage are
used for directional calculation.
If
Pol quantity is set to "Neg. seq. volt", the negative sequence current and negative
sequence voltage are used for directional calculation.
Protection functions
1MRS759142 F
454
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......