often encountered during the motor start-up and with abnormal conditions such as
locked rotor or unbalance, which both produce excess heat due to the skin effect.
The skin effect causes the current to distribute in a smaller surface in the rotor bars,
increasing the resistance, and therefore also the heating effect.
The function also provides locked rotor protection. The locked rotor condition can
be identified from the slip estimate that the function calculates.
4.1.11.4
Analog channel configuration
RPTTR has two analog group inputs which must be properly configured.
Table 485: Analog inputs
Input
Description
I3P
Three-phase currents
U3P
Three-phase voltages
4.1.11.5
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "on" and "off".
The operation of RPTTR can be described using a module diagram. All the modules
in the diagram are explained in the next sections.
The function uses ambient temperature which can be measured locally or remotely.
Local measurement is done by the protection relay. Remote measurement uses
analog IEC 61850-8-1 GOOSE to connect
AMB_TEMP
input.
If the quality of remotely measured temperature is invalid or
communication channel fails the function uses ambient temperature set
in
Env temperature Set.
Alarm and
tripping
logic
ALARM
OPERATE
BLK_RESTART
STALL_IND
START_EMERG
BLOCK
AMB_TEMP
U3P
I3P
U_A
U_B
U_C
I_A
I_B
I_C
I
2
Rotor
resistance
calculator
Max
current
selector
Internal
FLC
calculator
Thermal
level
calculator
TEMP_RL
Figure 245: RPTTR module diagram
Protection functions
1MRS759142 F
424
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......