Table 1204: Analog inputs
Input
Description
URES
1
Residual voltage (measured or calculated), necessary when
Wei mode
is set to "Echo and Operate"
See the preprocessing function blocks in this document for the possible
signal sources. The
GRPOFF
signal is available in the function block called
Protection.
There are a few special conditions which must be noted with the configuration.
Table 1205: Special conditions
Condition
Description
URES calculated
The function requires that all three voltage channels are con-
nected to calculate the residual voltage. Setting
VT connec-
tion
must be "Wye" in that particular UTVTR.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
5.13.5
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "on" and "off".
The operation of RCRWPSCH can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
CR
CB_OPEN
URES
ECHO
OPR_WEI
CR
Current
reversal
logic
Weak end
infeed
logic
BLK_WEI1
BLK_WEI2
FF
BLOCK
IRV
BLK_IRV
OPR_IRV
Uo
Figure 722: Functional module diagram
1
Can be connected to
GRPOFF
if
Wei mode is set to "Off" or "Echo".
1MRS759142 F
Protection related functions
REX640
Technical Manual
1275
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......