3.18.6
Received GOOSE interlocking information
GOOSERCV_INTL
3.18.6.1
Function block
Figure 99: Function block
3.18.6.2
Functionality
The received GOOSE interlocking information function GOOSERCV_INTL is used to
connect the GOOSE double binary input to the application and extracting single
binary position signals from the double binary position signal.
The
OP
output signal indicates that the position is open. Default value (0) is used if
VALID
output indicates invalid status.
The
CL
output signal indicates that the position is closed. Default value (0) is used if
VALID
output indicates invalid status.
The
OK
output signal indicates that the position is neither in faulty or intermediate
state. The default value (0) is used if
VALID
output indicates invalid status.
3.18.6.3
Signals
Table 149: GOOSERCV_INTL Input signals
Name
Type
Default
Description
IN
Dbpos
0
Input signal
Table 150: GOOSERCV_INTL Output signals
Name
Type
Description
OP
BOOLEAN
Position open output signal
CL
BOOLEAN
Position closed output signal
OK
BOOLEAN
Position OK output signal
VALID
BOOLEAN
Output signal
1MRS759142 F
Basic functions
REX640
Technical Manual
211
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......