9.11.6.5
Coil manual tuning
PASANCR supports manual coil tuning when
Controller mode setting is "Manual".
Manual control is achieved by activating
RAISE_LOCAL
and
LOWER_LOCAL
inputs
which activate the corresponding
RAISE_OWN
and
LOWER_OWN
outputs. The
manual mode and the corresponding inputs can be activated, for example, via
HMI application. Moreover, the manual control of the coil can be achieved via
communication by using the
Coil Target Pos setting. Once the setting is committed,
the controller moves to the desired position. Also the activated operating limits
can restrict the coil movement. The
MOT_ALARM
output is activated during manual
control if the coil position is not changed due to activated
RAISE_OWN
and
LOWER_OWN
commands. The
ALARM
output is activated when the movement of the
coil is in wrong direction or both end switches indicate simultaneously enabled
signaling.
Coil manual movement is possible only after calibration.
During the manual control mode the network resonance curve is not
updated automatically. The previous automatically detected resonance
curve is displayed on the HMI view.
It is possible to manually control the connection status of the fixed parallel coil with
Fix coil type setting by selecting "ON" or "OFF". The setting can be changed via the
settings menu or HMI application.
9.11.6.6
Resistor control
Zero-sequence currents in compensated networks are usually very low, making it
difficult to select the faulty line. To avoid sensitivity problems, the parallel resistor
of the ASC is often used to increase the zero-sequence current allowing a simple
earth-fault protection to locate the faulty line. PASANCR contains a functionality to
switch the resistor on and off automatically or on user input.
First, the resistor installation status is set with
Parallel resistor setting. The available
options are "True" and "False". If the parallel resistor is installed in the system, the
value is selected with
Resistor Nom value setting. Second, the nominal voltage level
of the power auxiliary winding is selected with
Auxiliary Wnd V Nom setting.
The
Resistor control setting is used to enable the automatic control sequence or to
connect or disconnect the resistor. The automatic control sequence is released if
the functionality is enabled (
Resistor control = "Automatic") and the
EARTH_FAULT
output is active. The resistor control sequence after the earth-fault indication
depends on the resistor connection status during the healthy state. The healthy-
state status is selected with the
Resistor healthy St setting. The available options
are "On" and "Off". The settings affecting the control sequence are explained in
.
1MRS759142 F
Control functions
REX640
Technical Manual
1743
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......