9.10.5.3
Operation mode selection
OL5ATCC has the
Operation mode and Parallel mode settings for selecting the
desired operation mode. The
Operation mode setting can have any of the following
values: "Manual", "Auto single", "Parallel manual", "Auto parallel", "Input control" and
“Command”. If the
Operation mode setting is set to "Input control", the active
operation mode is determined by the inputs
PARALLEL
and
AUTO
.
The
PARALLEL
input defines if the transformer (voltage regulator) is in parallel or
single mode. The
AUTO
input defines if the operation is in auto or manual mode.
The
PARALLEL
and
AUTO
outputs represent acting “Parallel or single operation” and
“Auto/Manual indication”, respectively.
When the
Operation mode setting is set to "Command", the active operation mode
is determined by the IEC 61850 command data points Auto and ParOp.
Furthermore, if the operation mode has been set to any parallel mode, that is
"Parallel manual" or "Auto parallel" via the
Operation mode setting, binary inputs or
commands, the parallel mode is selected by the setting
Parallel mode.
The
Parallel mode setting can have any of following values: "Master", "Follower",
"NRP", "MCC", "Input control" or "Command".
If the
Parallel mode setting is set to "Input control", the active operation mode is
determined by the input
MSTR_TRIGG
.
When the
Parallel mode setting is set to "Command", the active operation mode is
determined by the IEC 61850 command data point MstrOp.
MSTR_TRIGG
is a rising edge input, that is, the master role is kept even though
the
MSTR_TRIGG
input changes from “true” to “false”. This functionality is used
because another parallel transformer must be able to assume the master role even
though the
MSTR_TRIGG
input has remained in “true” state. Switching between
operation mode states resets the internal master set. However, switching between
Auto master mode and Parallel manual mode keeps the master role.
Table 1571: Active operation mode when Operation mode setting is "Manual",
"Auto single", "Parallel manual" or "Auto parallel"
Operation mode
Parallel mode
MSTR_TRIGG
OPR_MODE_STS
Manual
–
–
Manual
Auto single
–
–
Auto single
Parallel manual
Master
–
Parallel manual
Parallel manual
Input control Com-
mand
0
1
Manual
Parallel manual
Input control Com-
mand
1
1
Parallel manual
Auto parallel
Master
–
Auto master
Auto parallel
Follower
–
Auto follower
Auto parallel
MCC
–
MCC
Auto parallel
NRP
–
NRP
Table continues on the next page
1
The master role is set on rising edge and internally kept until another parallel transformer
assumes the master role, or the operation mode is changed.
1MRS759142 F
Control functions
REX640
Technical Manual
1699
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......