5.8.2
Function block
Figure 696: Function block
5.8.3
Functionality
The switch-onto-fault function CVPSOF is a complementary function, especially to
the distance protection function (DSTPDIS), but it can also be used to complement
the non-directional or directional overcurrent protection functions (PHxPTOC,
DPHxPDOC).
CVPSOF accelerates the operation of the protection ensuring a fast trip when
the breaker is closed onto faulted feeder or bus. Without CVPSOF the measured
voltages may be too small for the impedance zones or the directional overcurrent
stages to operate reliably. This condition exists when the voltage transformers are
located in the feeder or the bus side to be energized and therefore the voltage
memory required for a correct directional measurement is not available.
5.8.4
Analog channel configuration
CVPSOF has two analog group inputs which must be properly configured.
Table 1165: Analog inputs
Input
Description
I3P
1
Three-phase currents, necessary when Operation mode is
other than "Start"
U3P
2
Three-phase voltages, necessary when Operation mode is
other than "Start
See the preprocessing function blocks in this document for the possible
signal sources. The
GRPOFF
signal is available in the function block called
Protection.
There are a few special conditions which must be noted with the configuration.
1
Can be connected to
GRPOFF
if
Operation mode is set to "Start" and Automatic SOTF Ini is set to
"DLD disabled" or "Voltage"
2
Can be connected to
GRPOFF
if
Operation mode is set to "Start" and Automatic SOTF Ini is set to
"DLD disabled" or "Current"
1MRS759142 F
Protection related functions
REX640
Technical Manual
1223
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......