I
coil
Current of the adjustable ASC
I
fix
Value of the fixed parallel coil
I
reson
Current at resonance point
If a fixed parallel coil is introduced in the network (“ON” or “Automatic”), the x
axis title of the resonance curve displayed on the HMI can be selected with the
Resonance curve Cur setting. Available options are:
• Icoil: Only the current of adjustable ASC
• Icoil + Ifix: Total current of adjustable ASC and fixed parallel coil
Statistics
The controller supports displaying resettable statistics. The statistics can be reset
via settings menu using
Clear counters command.
Table 1590: Displayed statistics
Type
Statistics
Description
General
Operation time
Controller time in operation
Tuning procedures
Number of started tuning procedures
Tuned
Number of successful tuning operations
Canceled tunings
Number of the canceled tuning procedures,
that is,
Tuning delay
has not elapsed
Tuned at Uo max
Number of tuning cases when coil movement
has stopped to
V Res maximum
position
Tuned at low limit
Number of cases when coil final position is
limited either by low end position indication
of the coil or the limited operating range
Minimum current
Tuned at high limit
Number of cases when coil final position is
limited either by high end position indication
of the coil or the limited operating range
Maximum current
Earth faults
Transient earth-faults Number of transient earth faults (that is,
fault time shorter than time defined in
Tran-
sient time EF
setting)
Permanent earth-
faults
Number of permanent earth faults (that is,
fault time longer than time defined in
Transi-
ent time EF
setting)
Resistor control
Switch parallel resis-
tor (auto)
Number of parallel resistor switch opera-
tions. For example, if the resistor is initially
off, then it is switched on and after a defined
delay, it is again switched off, this increases
the counter by two.
Switch parallel resis-
tor (manual)
Number of manual switch operations for par-
allel resistor
Other
Motor running time
Sum time of
RAISE_OWN
and
LOWER_OWN
outputs activated
Control functions
1MRS759142 F
1742
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......