A DNP3 server protocol instance is activated if the function block instance is added
to the application configuration. The setting
Operation should be "On" and setting
Port should have the communication interface assignment.
The
STATUS
output of the function block is active if DNP3 client requests or DNP3
supervision messages have been received on the communication interface within an
interval defined by the link keep-alive parameter.
By default no DNP3 data is mapped to the protocol interface. Protocol data has to
be created using Communication Management in PCM600. There are two mapping
sets, “Mapping 1” and “Mapping 2”, and either can be used. Setting parameter
Mapping selection points to the mapping set used. Several DNP3 protocol instances
can point to the same mapping set.
For more information on the DNP3 server protocol, see the DNP3 communication
protocol manual.
3.2.15
IEC 60870-5-103 protocol I3CLPRT
3.2.15.1
Function block
I3CLPRT1
EC_FRZ
STATUS
Figure 21: Function block
3.2.15.2
Functionality
The function block represents one IEC 60870-5-103 server protocol instance in
the protection relay. Function block settings include communication interface
assignment for the instance, that is, serial communication port 1 or 2.
An IEC 60870-5-103 server protocol instance is activated if the function block
instance is added to the application configuration. The setting
Operation should be
"On" and setting
Serial port should have the communication interface assignment.
The
STATUS
output of the function block is active if IEC 60870-5-103 client requests
have been received on the communication interface within 15 seconds.
The function block input
EC_FRZ
relates to possible ASDU 205 (mostly energy)
counters defined in the protection relay. Activation of the
EC_FRZ
input freezes
and captures the current ASDU 205 counter values and sends them to the IEC
60870-5-103 client. Several options for the activation exist.
1. EC_FRZ object exists as a control object in the IEC 60870-5-103 data model, and
can be written from the client.
2.
EC_FRZ
physical input can be activated from an internal or external timer
application signal.
By default most IEC 60870-5-103 data is pre-mapped to the protocol interface.
However, protocol data can be deleted, added and modified using Communication
Management in PCM600.
For more information on the IEC 60870-5-103 server protocol, see the IEC
60870-5-103 communication protocol manual.
Basic functions
1MRS759142 F
96
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......