The cross (X) in the table defines when the operation is blocked (if the
corresponding bit is active in BLK_STATUS). For example, an overvoltage (runback
raising voltage) results in blocking only when the active operation mode is "Manual"
and the manual raising command is given.
Table 1575: Default blocking schema in OL5ATCC
Active
operation
mode
Comman
d
Load
current
Block
lower
voltage
Runback
raise
voltage
High
circulatin
g current
External
block
Extreme
positions
Manual,
Parallel
manual
Raise
X
X
X
Lower
X
X
Auto fol-
lower
Raise
X
X
X
X
Lower
X
X
X
X
Auto sin-
gle, Auto
master,
NRP, MCC
Raise
X
X
X
1
X
X
2
Lower
X
X
X
1
X
X
2
In addition to the default blocking, the
Custom Man blocking setting has been
added due to different operation practices of the manual command blocking.
The setting can be used to adapt blockings considering the manual overcurrent,
undervoltage or external blocking. (The blockings are in
in columns
Load current, Block lower voltage and External block for the manual operating
mode.) The default value for the parameter is "OC". This means that the default
blocking schema explained in
operates as such. However, there are other
alternatives that cause different operations.
Table 1576: Customized manual blocking schema
Manual
blocking
type
Enumeration
Description
1
Custom disabled No load current, block lower (under) voltage, external block-
ing has no effect in the manual operation modes
2
OC
Load current blocking has an effect in the manual operation
mode
3
UV
Block lowering (under) voltage blocking has an effect in the
manual operation mode
4
OC, UV
Conditions 2 and 3 together: Load current and block lowering
(under) voltage blocking have effect in the manual operation
mode
Table continues on the next page
1
Because the circulating current is calculated only in the NRP and MCC modes, it can have a
blocking effect only in these modes.
2
In these cases the automatic operation notices that the extreme position has already been
reached and there is no need to activate the signal for data set event sending. The automatic
follower case can here be compared to a manual case and an event can be sent, that is, the
corresponding output is activated.
1MRS759142 F
Control functions
REX640
Technical Manual
1717
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......