Connections
A special attention is paid to the connection of the protection relay. Furthermore it
is checked that the primary side wiring is correct.
A faulty wiring of the voltage inputs of the protection relay causes a malfunction in
the synchrocheck function. If the wires of an energizing input have changed places,
the polarity of the input voltage is reversed (180°). In this case, the protection relay
permits the circuit breaker closing in a situation where the voltages are in opposite
phases. This can damage the electrical devices in the primary circuit. Therefore, it is
extremely important that the wiring from the voltage transformers to the terminals
on the rear of the protection relay is consistent regarding the energizing inputs
U_BUS
(bus voltage) and
U_LINE
(line voltage).
The wiring should be verified by checking the reading of the phase difference
measured between the
U_BUS
and
U_LINE
voltages. The phase difference measured
by the protection relay has to be close to zero within the permitted accuracy
tolerances. The measured phase differences are indicated in the LHMI. At the
same time, it is recommended to check the voltage difference and the frequency
differences presented in the monitored data view. These values should be within the
permitted tolerances, that is, close to zero.
shows an example where the synchrocheck is used for the circuit breaker
closing between a busbar and a line. The phase-to-phase voltages are measured
from the busbar and also one phase-to-phase voltage from the line is measured.
Figure 852: Connection of voltages for the protection relay and signals used in
synchrocheck
9.5.7
Signals
1MRS759142 F
Control functions
REX640
Technical Manual
1553
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......