
Alternative 2 is more cost-effective and therefore often better, although the
sensitivity of the scheme is slightly reduced.
Example 2
Here the actions according to alternative 2 are taken to improve the actual
accuracy limit factor.
F
I CT
I Motor
F
a
R
R
n
=
×
(Equation 211)
I
R
CT
rated primary current of the CT, for example, 1500A
I
R
Motor
rated current of the motor under protection, for example, 1000A
F
n
rated accuracy limit factor of the CT, for example, 30
F
a
actual accuracy limit factor due to oversizing the CT, substituting the values in
the equation, F
a
= 45
In differential protection it is important that the accuracy limit factors F
a
of the phase current transformers at both sides correspond with each other,
that is, the burdens of the current transformers on both sides are to be as
close to each other as possible. If high inrush or start currents with high DC
components pass through the protected object when it is connected to the
network, special attention is required for the performance and the burdens
of the current transformers and the settings of the function block.
Connection of current transformers
The connections of the primary current transformers are designated as Type 1 and
Type 2.
• If the positive directions of the winding 1 and winding 2 protection relay currents
are opposite, the
CT connection type is of "Type 1". The connection examples of
"Type 1" are as shown in figures
• If the positive directions of the winding 1 and winding 2 protection relay currents
equate, the
CT connection type setting parameter is "Type 2". The connection
examples of "Type 2" are as shown in figures
.
• The default value of the
CT connection type setting is "Type 1".
Protection functions
1MRS759142 F
798
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......