while the fictive voltage is in use. When the voltage is below
Min operate voltage
and hysteresis and the fictive voltage is unusable, the fault direction cannot be
determined. The fictive voltage can be unusable for two reasons:
• The fictive voltage is discarded after
Voltage Mem time
• The phase angle cannot be reliably measured before the fault situation.
DPHxPDOC can be forced to the non-directional operation with the
NON_DIR
input. When the
NON_DIR
input is active, DPHxPDOC operates as a non-directional
overcurrent protection, regardless of the
Directional mode setting.
Figure 207: Operating zones at minimum magnitude levels
The
DIRECTION
output indicates on which operating sector the current is
measured. The value combines phase-specific directions which are available in
monitored data as DIR_A, DIR_B and DIR_C.
Level detector
The measured phase currents are compared phasewise to the set
Start value. If the
measured value exceeds the set
Start value, the level detector reports the exceeding
of the value to the phase selection logic. If the
ENA_MULT
input is active, the
Start
value setting is multiplied by the Start value Mult setting.
The protection relay does not accept the
Start value or Start value Mult
setting if the product of these settings exceeds the
Start value setting
range.
Protection functions
1MRS759142 F
348
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......