Alarm limit check
When the inactive days exceed the limit value defined with the
Inactive Alm days
setting, the
MON_ALM
alarm is initiated. The time in hours at which this alarm is
activated can be set with the
Inactive Alm hours parameter as coordinates of UTC.
The alarm signal
MON_ALM
can be blocked by activating the binary input
BLOCK
.
7.1.5.3
Breaker contact travel time
The Breaker contact travel time module calculates the breaker contact travel time
for the closing and opening operation. The operation of the breaker contact travel
time measurement can be described with a module diagram. All the modules in the
diagram are explained in the next sections.
Figure 774: Functional module diagram for breaker contact travel time
Traveling time calculator
The travel time can be calculated using two different methods based on the setting
Travel time Clc mode.
When the setting
Travel time Clc mode is “From Pos to Pos”, the contact travel time
of the breaker is calculated from the time between auxiliary contacts' state change.
The opening travel time is measured between the opening of the
POSCLOSE
auxiliary
contact and the closing of the
POSOPEN
auxiliary contact. The travel time is also
measured between the opening of the
POSOPEN
auxiliary contact and the closing of
the
POSCLOSE
auxiliary contact.
Figure 775: Travel time calculation when Travel time Clc mode is “From Pos to Pos”
There is a time difference t
1
between the start of the main contact opening and
the opening of the
POSCLOSE
auxiliary contact. Similarly, there is a time gap t
2
1MRS759142 F
Condition monitoring functions
REX640
Technical Manual
1363
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......