Synchroni-
zation
check and
control
CB_CLOSE
CB_OPEN
LADB
LALB
DALB
DADB
EXT_CHECK
CB_TEST
ISO_A1_CLOSE
ISO_A2_CLOSE
ISO_B1_CLOSE
ISO_B2_CLOSE
SYNC_INPRO
SYNC_OK
CL_FAIL_AL
CMD_FAIL_AL
MATCH_INPRO
MATCH_OK
CLOSE_CB
ASC1_NS_DAT
Energizing
check
U3P1
U3P2
CL_COMMAND
U_A_AB
U_B_BC
U_C_CA
BYPASS
BLOCK
U_A_AB
CB_SELECTED
NS_ASC_DAT
U_DIFF
FR_DIFF_MEAS
AS_INIT_FAIL
CL_FAIL_AL
CL_FAIL_AL
CL_FAIL_AL
Figure 870: Functional module diagram
This function can operate either with the U_AB or U_A voltages. The selection
of used voltages is defined with the
VT connection of the line voltage general
parameters.
9.7.5.1
Energizing check
The Energizing check module checks the energizing direction. Energizing is the
situation where a dead network part is connected to an energized section of the
network. The
Live dead mode setting is used to set the energized condition of the
bus section across the CB, that is, whether the bus section across the CB is live or
dead..
When the
Live dead mode setting parameter is set to "Command", then
then the energized condition (see
) of bus sections across the
CB can be set using the
Live dead mode Ctl control command only. If the
Live dead mode setting parameter is not set to "Command", then the
Live dead mode setting parameter is used to set the energized condition
) of the bus section across the CB.
1MRS759142 F
Control functions
REX640
Technical Manual
1589
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......