θ
θ
h
hr
y
k
K
1 0
21
(Equation 331)
∆
=
−
(
)
⋅ ∆
⋅
( )
θ
θ
h
hr
y
k
K
2 0
21
1
(Equation 332)
The final hot-spot temperature is calculated as the sum of top oil temperature and
the rise of hot-spot temperature over the top oil temperature.
The hot-spot temperature at the nth time step is calculated as shown in
.
HOTSPOT
TEMP
o n
h n
_
( )
( )
=
+ ∆
θ
θ
(Equation 333)
The calculated hot-spot temperature HOTSPOT_TEMP and rated hot-spot to top oil
gradient, HS_TOIL_GRA are available in the Monitored data view.
7.3.5.4
Level detector 1
This module compares the calculated hot-spot temperature, HOTSPOT_TEMP value
with the
Alarm level and Warning level settings.
If HOTSPOT_TEMP is greater than the
Warning level, the module activates the
WARNING
output after a settable
Warning delay time.
If HOTSPOT_TEMP is greater than the
Alarm level, the module activates the
ALARM
output after a settable
Alarm delay time.
Assuming existing conditions, as long as the alarm/warning conditions are
not reached, the module calculates the available load reserve in percentage to
reach the alarm condition
LD_RSV_ALM_PCT
and to reach the warning condition,
LD_RSV_WRN_PCT
. These outputs can be obtained from the Monitored data view.
If the warning condition is reached, the
LD_RSV_WRN_PCT
output is forced to zero
and if the alarm condition is reached,
LD_RSV_ALM_PCT
is forced to zero.
The load reserve outputs are only indicative and are calculated based
on rated current, assuming the same ambient temperature and cooling
modes. If, for any reason, the load reserve calculation is not feasible, the
load reserve outputs are shown as zero.
The binary input
BLOCK
can be used to block the function. The activation of the
BLOCK
input deactivates
WARNING
and
ALARM
outputs and resets the internal timers.
7.3.5.5
Ageing and loss of life calculation
This module calculates the rate at which transformer insulation ageing is
accelerating compared with the ageing rate at rated hot-spot temperature and
equivalent ageing over a time period.
If transformer insulation paper is not upgraded, that is, if setting
Insul paper type is
set to "Normal", the setting
Ageing rate method selects between the IEC and IEEE
1MRS759142 F
Condition monitoring functions
REX640
Technical Manual
1389
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......