Parameter
Values (Range)
Unit
Step
Default
Description
5=off
Ps Seq A Hi high
Lim
0.00...40.00
xIn
0.01
1.40
High alarm current
limit for positive
sequence current
Ps Seq A high limit
0.00...40.00
xIn
0.01
1.20
High warning cur-
rent limit for pos-
itive sequence cur-
rent
Ps Seq A low limit
0.00...40.00
xIn
0.01
0.00
Low warning cur-
rent limit for pos-
itive sequence cur-
rent
Ps Seq A low low
Lim
0.00...40.00
xIn
0.01
0.00
Low alarm current
limit for positive
sequence current
Ps Seq A deadband 100...100000
1
2500
Deadband configu-
ration value for
positive sequence
current for inte-
gral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Ng Seq A Hi high
Lim
0.00...40.00
xIn
0.01
0.20
High alarm current
limit for negative
sequence current
Ng Seq A High limit 0.00...40.00
xIn
0.01
0.05
High warning cur-
rent limit for neg-
ative sequence cur-
rent
Ng Seq A low limit
0.00...40.00
xIn
0.01
0.00
Low warning cur-
rent limit for neg-
ative sequence cur-
rent
Ng Seq A low low
Lim
0.00...40.00
xIn
0.01
0.00
Low alarm current
limit for negative
sequence current
Ng Seq A deadband 100...100000
1
2500
Deadband configu-
ration value for
negative sequence
current for inte-
gral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Zro A Hi high Lim
0.00...40.00
xIn
0.01
0.20
High alarm current
limit for zero se-
quence current
Zro A High limit
0.00...40.00
xIn
0.01
0.05
High warning cur-
rent limit for zero
sequence current
Zro A low limit
0.00...40.00
xIn
0.01
0.00
Low warning cur-
rent limit for zero
sequence current
Zro A low low Lim
0.00...40.00
xIn
0.01
0.00
Low alarm current
limit for zero se-
quence current
Zro A deadband
100...100000
1
2500
Deadband configu-
ration value for
zero sequence cur-
rent for integral cal-
culation. (percent-
age of difference
between min and
max as 0,001 % s)
1MRS759142 F
Measurement functions
REX640
Technical Manual
1473
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......