
In the permissive underreach scheme, the start signal from the underreaching zone
Z1 is connected to the
CSUR
input to create a
CS_PRM
signal. The duration of the
CSUR
input signal can be prolonged by the
Carrier Min Dur setting to ensure a
sufficient duration of the
CS_PRM
signal.
In the permissive underreach scheme, the
CS_PRM
signal, or the
CRL
signal if the
unblocking function is enabled, is used to allow the overreaching zone Z2 to trip
(activation of the
OPERATE
output) after the pick-up delay
Coordination Time. The
start signal from the overreaching zone Z2 is connected to the
CACC
input.
Activating the
BLOCK
input totally blocks the permissive underreach scheme. The
CS_PRM
and
OPERATE
outputs can be blocked by the
BLK_CS_OPR
input.
Z2
Z2
Bus A
Bus B
~
~
Z1
Z1
CB_A
CB_B
Z2_START
TRIP_CB_A
TRIP_CB_B
Z1_START
Z2_START
3
3
Figure 705: Simplified functional diagram of the permissive underreach scheme
Permissive overrreaching transfer trip scheme POTT
The permissive overreach scheme is enabled with
Scheme type = "Permissive
Overreach".
In this scheme, the start signal from the overreaching zone Z2 is connected to
the
CSOR
input to create a
CS_PRM
signal. The
CS_PRM
signal can also be issued
simultaneously from the underreaching zone Z1. In this case, the start signal from
the underreaching zone Z1 is connected to the
CSUR
input. The duration of the
CSUR
input signal is prolonged by the
Carrier Min Dur setting to ensure a sufficient
duration of the
CS_PRM
signal.
In case of parallel feeders, and when the external current reversal logic
(CRWPSCH) is enabled, the
CS_PRM
signal is not prolonged and the value
of
Carrier Min Dur is set to zero to secure correct operation.
Protection related functions
1MRS759142 F
1240
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......