Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
5.4.5
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "On" and "Off".
PHIZ uses a multi-algorithm approach. Each algorithm uses various features of
earth currents to detect a high-impedance fault.
Although the PHIZ algorithm is very sophisticated, the setting required to operate
the function is simple. The
Security Level setting, with the setting range of 1 to
10, is set to strike a balance between the extremes of security and dependability
which together constitute the reliability of any system. The setting value “10” is
more secure than “1”.
The higher the
Security Level setting, the lower the probability of false detection,
but the system might miss out some genuine fault. On the other hand, a lower
setting would make the system operate more dependably for high-impedance
faults in the line, but the operation is more likely for other transients in the
system. There are events in electrical networks which can cause similar current
waveforms like high-impedance faults. These events could then be detected by
the PHIZ algorithm causing unnecessary detections. Normally, electrical network
operator does not know the existence of these events well and those can also be
happening very randomly. The effect is also always dependent on event location
compared to protection relay measurement location. All these facts make the
PHIZ algorithm operation in certain electrical networks quite hard to measure and
forecast beforehand. There is not any direct formula which can calculate the exact
right setting based on known electrical network parameters.
It is hence recommended to set the value midway to “5” initially. Based on
experience and confidence gained in a particular application, the setting can be
moved either side. In many cases, it would be a good practice to use PHIZ as
an indicative function during a piloting phase, until enough experience has been
gathered and a suitable setting found.
Transformer
Feeder
Bus
Ct
Breaker
Figure 670: Electrical power system equipped with PHIZ
Protection related functions
1MRS759142 F
1180
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......