Description
Value
Threshold voltage
16...176 V DC
Ripple in the DC auxiliary voltage
Max 15 % of the DC value (at frequency of 100
Hz)
Wetting current
220 mA, impulse period 5ms
0…120
mA
10
, impulse period 8ms
Adjust the binary input threshold voltage correctly. It is recommended
to set the threshold voltage to 70 % of the nominal auxiliary voltage.
The factory default is 16 V to ensure the binary inputs’ operation
regardless of the auxiliary voltage used (24, 48, 60, 110, 125, 220 or 250 V
DC). However, the default value is not optimal for the higher auxiliary
voltages. The binary input threshold voltage should be set as high
as possible to prevent any inadvertent activation of the binary inputs
due to possible external disturbances. At the same time, the threshold
should be set so that the correct operation is not jeopardized in case of
undervoltage of the auxiliary voltage.
Table 1671: RTD/mA inputs and mA outputs
Description
Value
RTD inputs
Supported RTD sen-
sors
100 Ω platinum
250 Ω platinum
100 Ω nickel
120 Ω nickel
250 Ω nickel
TCR 0.00385 (DIN
43760)
TCR 0.00385
TCR 0.00618 (DIN
43760)
TCR 0.00618
TCR 0.00618
Supported resistance
range
0...4 kΩ
Maximum lead re-
sistance (three-wire
measurement)
100 Ω per lead
Isolation
2 kV (inputs to protective earth)
Response time
<1 s
RTD/resistance sens-
ing current
<1 mA rms
Operation accuracy
Resistance
Temperature
± 2.0 % or ±1 Ω
±1°C
mA inputs
Supported current
range
±0…20 mA
Current input impe-
dance
44 Ω ±0.1 %
Operation accuracy
±0.5 % or ±0.01 mA
mA outputs
Supported current
range
±0…20 mA
Table continues on the next page
10
Adjustable only in RTD1002 module
1MRS759142 F
Technical data
REX640
Technical Manual
1943
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......