also the
DIPST
outputs are activated. When the TRMS voltage magnitude remains
between
Voltage dip set 2 and Voltage dip set 1 for a period longer than VVa dip
time 2 (shorter time than VVa dip time 3), a momentary dip event is detected.
Furthermore, if the signal magnitude stays between the limits longer than
VVa dip
time 3 (shorter time than VVa Dur max), a temporary dip event is detected. If the
voltage remains below
Voltage dip set 1 for a period longer than VVa dip time 1 but a
shorter time than
VVa dip time 2, an instantaneous dip event is detected.
For an event detection, the
OPERATE
output is always activated for one task cycle.
The corresponding counter and only one of them (INSTDIPCNT, MOMDIPCNT or
TEMPDIPCNT) is increased by one. If the dip limit undershooting duration is shorter
than
VVa dip time 1, VVa swell time 1 or VVa Int time 1, the event is not detected
at all, and if the duration is longer than
VVa Dur Max, MAXDURDIPCNT is increased
by one but no event detection resulting in the activation of the
OPERATE
output
and recording data update takes place. These counters are available through the
monitored data view on the LHMI or through tools via communications. There are
no phase-segregated counters but all the variation detections are registered to
a common time/magnitude-classified counter type. Consequently, a simultaneous
multiphase event, that is, the variation-type event detection time moment is exactly
the same for two or more phases, is counted only once also for single-phase power
systems.
Voltage dip set 1
Voltage dip set 2
Voltage dip set 3
Voltage
xUref
Time (ms)
0
0
VVa Dur Max
VVa dip time 3
VVa dip time 1
VVa dip time 2
1.00
Instantaneous
dip
Temporary
dip
Momentary
dip
Maximum duration
dip
Figure 970: Voltage dip operational regions
, the corresponding limits regarding the swell operation are provided
with the inherent magnitude limit order difference. The swell functionality principle
is the same as for dips, but the different limits for the signal magnitude and times
and the inherent operating zone change (here,
Voltage swell set x > 1.0 xUn) are
applied.
Power quality measurement functions
1MRS759142 F
1834
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......