where t
FLT
(1) equals the first time instant, when earth fault is detected by the GFC-
module. Pre-fault time moment is at least
Revert time before earth fault occurrence
moment.
Revert time setting should be set high enough (default value is 300 ms), because
during a high(er) ohmic fault the increase speed (gradient) of the magnitude of
U
o
may be slow, refer to example in
, where earth-fault occurs at time 0
ms. Earth fault is detected by GFC module slightly after that, at time instant t
FLT
(1)
marked with red dot, when magnitude of U
o
exceeds setting
Voltage start value. As
an indication of detected earth-fault output
EF_IND
is activated.
Figure 337: Illustration of operation of General Fault Criterion (GFC) module and the meaning of
setting Revert time
In case of secondary testing of IFPTOC function, the pre-fault time in the
test file must be longer than
2xRevert time. For example, if Revert time =
300 ms, then pre-fault time in the test file must be longer than 600 ms.
Indication of detected earth fault is available in Recorded data:
EF
indication.
Fault current estimation and validity check
Operation of IFPTOC is based on estimating the magnitude of earth-fault current
flowing in the fault spot, or on touch voltage magnitude derived from the earth-
fault current estimate.
In compensated network, the magnitude of fundamental frequency earth-fault
current depends on the network damping (
I
d
), detuning (
I
v
), voltage (
U
PE
) and fault
resistance (
R
F
) and can be written as:
Protection functions
1MRS759142 F
588
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......