4.2.3.8
INTRPTEF Settings
Table 559: INTRPTEF Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Operate delay time 40...1200000
ms
10
500
Operate delay time
Voltage start value 0.05...0.50
xUn
0.01
0.20
Voltage start value
Table 560: INTRPTEF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Operation mode
1=Intermittent EF
2=Transient EF
1=Intermittent EF
Operation criteria
Table 561: INTRPTEF Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
40...60000
ms
1
500
Reset delay time
Peak counter limit
2...20
1
2
Min requirement
for peak counter
before start in IEF
mode
Min operate current 0.01...1.00
xIn
0.01
0.01
Minimum operating
current for transi-
ent detector
4.2.3.9
INTRPTEF Monitored data
Table 562: INTRPTEF Monitored data
Name
Type
Values (Range)
Unit
Description
FAULT_DIR
Enum
0=unknown
1=forward
2=backward
3=both
Detected fault direction
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
INTRPTEF
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS759142 F
Protection functions
REX640
Technical Manual
489
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......