
10.3.5
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of PHQVVR can be described with a module diagram. All the modules
in the diagram are explained in the next sections.
BLOCK
Duration
measurement
U3P
I3P
U_A
U_B
U_C
Variation
detection
Variation
validation
Recorded
data
SWELLST
DIPST
INTST
START
OPERATE
I_A
I_B
I_C
Figure 968: Functional module diagram
10.3.5.1
Phase mode setting
PHQVVR is designed for both single-phase and polyphase ac power systems, and
selection can be made with the
Phase mode setting, which can be set either to the
"Single Phase" or "Three Phase" mode. The default setting is "Single Phase".
The basic difference between these alternatives depends on how many phases are
needed to have the voltage variation activated. When the
Phase mode setting is
"Single Phase", the activation is straightforward. There is no dependence between
the phases for variation start. The
START
output and the corresponding phase
start are activated when the limit is exceeded or undershot. The corresponding
phase start deactivation takes place when the limit (includes small hysteresis) is
undershot or exceeded. The
START
output is deactivated when there are no more
active phases.
However, when
Phase mode is "Three Phase", all the monitored phase signal
magnitudes, defined with
Phase supervision, have to fall below or rise above the
limit setting to activate the
START
output and the corresponding phase output,
that is, all the monitored phases have to be activated. Accordingly, the deactivation
occurs when the activation requirement is not fulfilled, that is, one or more
monitored phase signal magnitudes return beyond their limits. Phases do not need
to be activated by the same variation type to activate the
START
output. Another
consequence is that if only one or two phases are monitored, it is sufficient that
these monitored phases activate the
START
output.
1MRS759142 F
Power quality measurement functions
REX640
Technical Manual
1831
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......