The length of the voltage raise and lower command pulse (tpU) and the pulse off
interval (tsU) are calculated based on the setting
Voltage match mode.
Voltage matching in manual mode
If
Auto Syn mode is set to "Manual mode", the voltage raise or lower command
pulses are generated manually from the function's user commands.
If the command
AVR voltage raise is set to "RAISE", the function activates the
voltage raise command pulse
RAISE_U
. If the command
AVR voltage lower is set to
"LOWER", the function activates the voltage lower command pulse
LOWER_U
.
The lengths of these generated pulses tpU and pulse off interval tsU are based on
the settings as: tpU =
Volt pulse Min Dur; tsU = Volt pulse off Intv.
Voltage matching with variable command pulse lengths
When the setting
Voltage match mode is set to "Variable Pulse", the voltage
matching is done with variable command pulse lengths.
The voltage matcher issues a command with a length proportional to the voltage
difference. The proportionality factor setting
Volt rate of change (dU/dt) can be
adapted to the voltage regulator. The voltage matcher aims at a value in the middle
of the set tolerance band.
The adjusting voltage command pulse length tpU is calculated as
tpU
U
U
U
dU
dt
=
−
+
− −
∆
∆
∆
max
max
2
(Equation 360)
ΔU
Measured voltage difference across the CB to be synchronized
+ΔUmax
Setting
Voltage Diff Ov Ex
-ΔUmax
Setting
Voltage Diff Un Ex
dU/dt
Setting
Volt rate of change
The adjusting pulse is discontinued as soon as the voltage difference exceeds the
target value. The command length does not fall below a settable minimum value
Volt
pulse Min Dur. After an adjusting command, the system waits for the set Volt pulse
off Intv (tsU) so that the actual values can stabilize to the new set point.
Control functions
1MRS759142 F
1572
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......