The operation of a particular zone is given after the set operate delay time for the
particular zone has elapsed (considering the fault type). The actual operate time
is the value calculated from the initial fault detection and it is not affected, for
example, in case the fault moves between zones.
The general indication of fault for each zone is given in the
START_Zx
(x = 1...5)
binary output. The faulted phase information can be found from the STARTS_Zx
(x = 1... 5) integer type output signal. This signal indicates (bitwise) the started
measuring elements for the corresponding phase. Value 0 does not exist but due
to the IEC 61850 standard requirement, it is shown by value “-5” as “No fault”.
Value range is thus -5, 1..63. The three-phase fault is here indicated by “AB Fault, BC
Fault, CA Fault”. However, three-phase fault indication for GFC depends also on the
additional condition for voltage (see
).
Table 920: STARTS_Zx information
Value
Value information
-5
No zone starts
1
AG Fault
2
BG Fault
3
AG Fault, BG Fault
4
CG Fault
5
AG Fault, CG Fault
6
BG Fault, CG Fault
7
AG Fault, BG Fault, CG Fault
8
AB Fault
9
AG Fault, AB Fault
10
BG Fault, AB Fault
11
AG Fault, BG Fault, AB Fault
12
CG Fault, AB Fault
13
AG Fault, CG Fault, AB Fault
14
BG Fault, CG Fault, AB Fault
15
AG Fault, BG Fault, CG Fault, AB Fault
16
BC Fault
17
AG Fault, BC Fault
18
BG Fault, BC Fault
19
AG Fault, BG Fault, BC Fault
20
CG Fault, BC Fault
21
AG Fault, CG Fault, BC Fault
22
BG Fault, CG Fault, BC Fault
23
AG Fault, BG Fault, CG Fault, BC Fault
24
AB Fault, BC Fault
25
AG Fault, AB Fault, BC Fault
26
BG Fault, AB Fault, BC Fault
27
AG Fault, BG Fault, AB Fault, BC Fault
28
CG Fault, AB Fault, BC Fault
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
963
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......