R
1
Estimated positive-sequence resistance from the substation to the fault loca-
tion
X
1
Estimated positive-sequence reactance from the substation to the fault loca-
tion
R
0
Estimated zero-sequence resistance from the substation to the fault location
X
0
Estimated zero-sequence reactance from the substation to the fault location
R
N
Estimated the earth return path resistance (= (R0 – R1)/3) from the substation
to the fault location
X
N
Estimated is the earth return path reactance (= (X0 – X1)/3) from the substa-
tion to the fault
R
fault
Estimated fault resistance at the fault location
The recorded data Flt phase reactance provides the estimated positive-sequence
reactance from the substation to the fault location.
Figure 683: Fault loop impedance for phase-to-earth fault loops “AG Fault”, “BG
Fault” or “CG Fault”
Setting
Flt Loc Det mode is used for selecting between different algorithms for the
calculation of the earth-fault distance. In case of compensated (resonant earthed)
networks where an earth-fault current raising resistor is used, setting
Flt Loc Det
mode = "Comp, switched R" should be selected. In all other cases of system neutral
point earthing (effectively earthed, low-resistance, low-reactance or unearthed
networks), setting "Non-comp" should be selected.
Earth-fault distance calculation in case of non-compensated networks
In case of non-compensated networks (effectively earthed, low-resistance,
lowreactance or unearthed networks), the setting
Flt Loc Det mode is equal to
"Noncomp". Furthermore, the earth-fault distance calculation algorithm is selected
with setting
EF algorithm Sel. Options for the selection are "Load compensation"
and "Load modelling". For the correct operation of both algorithms, there should
not be any zero-sequence current sources, for example, earthing transformers, in
front of the protection relay.
The “Load compensation” algorithm uses symmetrical components to compensate
for the effect of load on the measured voltages and currents. In case of radial
feeders, this algorithm should be selected with low-impedance/effectively earthed
systems where the fault current is fed from one side only and there are no in-feeds
along the protected line.
The “Load modelling” algorithm takes into account the effect of the load in the
measured currents and voltages by considering it in the fault loop model. In case
Protection related functions
1MRS759142 F
1198
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......