Iosin(φ) and Iocos(φ) criteria
A more modern approach to directional protection is the active or reactive current
measurement. The operating characteristic of the directional operation depends
on the earthing principle of the network. The Iosin(φ) characteristics is used in an
isolated network, measuring the reactive component of the fault current caused
by the earth capacitance. The Iocos(φ) characteristics is used in a compensated
network, measuring the active component of the fault current.
The operation criteria Iosin(φ) and Iocos(φ) are selected with the
Operation mode
setting using the values "IoSin" or "IoCos" respectively.
The angle correction setting can be used to improve selectivity. The setting
decreases the operation sector. The correction can only be used with the Iosin(φ) or
Iocos(φ) criterion. The
RCA_CTL
input is used to change the Io characteristic:
Table 538: Relay characteristic angle control in the IoSin and IoCos operation
criteria
Operation mode:
RCA_CTL
= "False"
RCA_CTL
= "True"
IoSin
Actual operation criterion: Io-
sin(φ)
Actual operation criterion: Io-
cos(φ)
IoCos
Actual operation criterion: Io-
cos(φ)
Actual operation criterion: Io-
sin(φ)
When the Iosin(φ) or Iocos(φ) criterion is used, the component indicates a forward-
or reverse-type fault through the
FAULT_DIR
and
DIRECTION
outputs, in which 1
equals a forward fault and 2 equals a reverse fault. Directional operation is not
allowed (the
Allow non dir setting is "False") when the measured polarizing or
operating quantities are not valid, that is, when their magnitude is below the set
minimum values. The minimum values can be defined with the
Min operate current
and
Min operate voltage settings. In case of low magnitude, the
FAULT_DIR
and
DIRECTION
outputs are set to 0 = unknown, except when the
Allow non dir setting
is "True". In that case, the function is allowed to operate in the directional mode as
non-directional, since the directional information is invalid.
The calculated Iosin(φ) or Iocos(φ) current used in direction determination can be
read through the I_OPER monitored data. The value can be passed directly to a
decisive element, which provides the final start and operate signals.
The I_OPER monitored data gives an absolute value of the calculated
current.
The following examples show the characteristics of the different operation criteria:
Example 1.
Iosin(φ) criterion selected, forward-type fault
=> FAULT_DIR = 1
1MRS759142 F
Protection functions
REX640
Technical Manual
467
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......