which cause the heating to be rapid. This prevents premature degeneration of the
rotor unit. Additionally, the function provides an estimate of the motor slip, which
allows identify locked rotor. This function is applicable for direct-on-line started
induction motors with the motor line voltages available.
The rotor thermal overload protection function should be used in parallel with the
motor thermal overload protection function MPTTR. This way both, the more rapid
heating of the rotor, and the stable heating of the entire motor are taken into
account.
Abnormal conditions that can result in overheating the rotor include overload,
stalling, failure to start, high ambient temperature, restricted motor ventilation,
reduced speed operation, frequent starting or jogging, high or low line voltage
or frequency, mechanical failure of the driven load, improper installation, and
unbalanced line voltage or single phasing. Protecting from insulation failure by
implementation of current sensing alone cannot detect all of these conditions, such
as restricted ventilation. Similarly, protection by sensing temperature alone may be
inadequate, in cases like frequent starting or jogging. Thermal overload protection
addresses these deficiencies to a large extent by deploying a rotor thermal model
based on load current and the load voltage.
Rotor thermal level is calculated based on the rotor resistance factors, True RMS
phase currents and negative sequence current. The rotor resistance factor is based
on the estimated slip, that is calculated based on the measured line voltage and
measured load current.
In addition, motor ambient temperature is taken into account in the thermal level
calculation. Apart from current and the rotor resistance factor, the rate at which
rotor heats up or cools is governed by time constant of the rotor.
Selecting of weighing factor
Motor manufacturers usually define two thermal limit curves one for warm and
one for cold starts. The demands that these curves set are answered with the
corresponding relay curves
.
Protection functions
1MRS759142 F
430
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......