to capacitor manufacturing tolerances. The natural unbalance current must be
compensated for before using the measured unbalance current for the function
operation. The natural unbalance current needs to be recorded when there is no
fault in the capacitor banks, and it is initiated through the command
Record
unbalance, available under menu path Control > CUBPTOC. By selecting Record
unbalance with value “Record”, the measured unbalance current
I
Unb
is considered
as the natural unbalance current
I
NatUnb
and is stored as a reference. The amplitude
and angle of the recorded natural unbalance current I_AMPL_NAT and I_ANGL_NAT
are available in the monitored data view.
Once the natural unbalance current is recorded during further executions of the
function, the natural unbalance current is subtracted from the measured unbalance
current
I
Unb
to obtain the compensated unbalance current
I
CompUnb
as shown in
Figure 630: Natural unbalance compensation. (a) Healthy condition when the natural
unbalance is recorded (b) Unbalance compensation during faulty conditions
The natural unbalance current compensation is enabled using the setting
Natural
Comp Enable. If Natural Comp Enable is set to “FALSE”, the unbalance current is not
compensated. If
Natural Comp Enable is set to “TRUE”, the compensated unbalance
current is calculated based on the equation.
I
I
I
CompUnb
Unb
NatUnb
=
−
(Equation 286)
The amplitude I_AMPL_COMP and the angle I_ANGL_COMP of the compensated
unbalance current
I
CompUnb
are available in the monitored data view.
Protection functions
1MRS759142 F
1122
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......