3.20.3.2
Function block
Figure 128: Function block
3.20.3.3
Functionality
The daily timer function DTMGAPC is used to activate or deactivate its output at the
set time of the day. It is possible to set a different activation or deactivation time
separately for each day of the week.
3.20.3.4
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "on" and "off".
The operation of DTMGAPC can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
Q
Time
comparator
BLOCK
FREEZE
Figure 129: Functional module diagram
Time comparator
This module compares the current day and time with the activation hour and minute
defined with the settings
xxx Act hour and xxx Act Mn, respectively. When the time
of the day reaches the set activation time, output
Q
is activated and remains active
for the duration defined by the setting
xxx off delay.
The output remains active until the next day if the value for
xxx off delay
is set so that it results into rollover of the day.
Different activation and deactivation times can be set for all days of the week. The
activation and deactivation can also be disabled for a specific day. For example, if
the activation or deactivation is not needed on Sundays, the setting
Sunday Act
enable can be set as "False".
Activation of the
BLOCK
input deactivates the function output whereas the
activation of the
FREEZE
input freezes the output. The
BLOCK
input always has a
higher priority than the
FREEZE
input.
3.20.3.5
Application
DTMGAPC is useful in applications that require signal activation and deactivation
at a specific time of the day. Different activation times and duration can be set for
Basic functions
1MRS759142 F
238
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......