Parameter
Values (Range)
Unit
Step
Default
Description
DT stage Op time
100...60000
ms
10
500
Operate delay time
for Touch volt-
age/fault current
estimation module,
DT timer
IDMT stage Min Op
Tm
50...6000
ms
10
100
Minimum operate
delay for touch
voltage/fault cur-
rent estimation
module IDMT tim-
er according to
standard EN50522/
IEEE80
IDMT stage Max Op
Tm
500...7200000
ms
10
10000
Maximum operate
delay for touch
voltage/fault cur-
rent estimation
module IDMT tim-
er according to
standard EN50522/
IEEE80
UTp multiplier
0.10...5.00
0.01
1.00
UTp multiplier for
IDMT curve accord-
ing to standard
EN50522
Reduction factor
0.10...1.00
0.01
1.00
Reduction factor
in the touch volt-
age/fault current
estimation mod-
ule according to
standard EN50522/
IEEE80
Maximum earthing
Ris
0.5...1000.0
ohm
0.1
10.0
Maximum earthing
resistance encoun-
tered in the protec-
ted feeder in pri-
mary ohms accord-
ing to standard
EN50522/IEEE80
IEEE multiplier
50.0...5000.0
0.1
157.0
Multiplier accord-
ing to standard
IEEE80
XC stage A Str Val
0.10...5.00
xIn
0.01
1.00
Current threshold
for cross-country
fault module. Note
that In means
phase nominal cur-
rent
XC stage PP V Val
0.01...1.00
xUn
0.01
0.90
Phase-to-phase
voltage threshold
for cross-country
fault detection
module. Note that
Un means phase to
phase nominal volt-
age.
XC stage Op time
60...60000
ms
10
200
Operate delay time
for cross-country
fault detection
stage
Intr EF operate
time
100...10000
ms
10
1000
Operate delay time
during intermittent
earth fault
Table 640: IFPTOC Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
EF validity Op
mode
1=Resistive
2=Resistive, Reac-
tive
2=Resistive, Reac-
tive
EF validity opera-
tion mode
Table continues on the next page
Protection functions
1MRS759142 F
640
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......