• DISA_1_2 is FALSE
• GRAD_FAIL is FALSE
• Setting Ena 1st Ph transfer is “1>2” or “both”
• READY (from Evaluation module) is TRUE
• If transfer is initiated manually, then ENA_FASTONLY must be FALSE
First the main supply feeder will be opened without delay. Once the supply feeder
breaker opens, the connected busbar is without power supply and will run down in
accordance with its specific characteristic curve.
For the connection of the stand-by feeder, variety of points in time are possible at
which circuit breaker closing is possible with minimal stress to the system. Closing
of the circuit breaker is timed is such way that at the closing time of the breaker,
phase angle difference between stand-by feeder and busbar is close to zero.
The HSABTC determines the course of the difference voltage and the point in
time of the 1st phase coincidence through anticipatory computation. In order to
compensate for the installation-specific processing time (system response time,
circuit breaker operating time), the close command is issued accordingly before the
actual first minimum of the difference voltage occurs within a previously defined
connection window.
1
2
3
4
5
6
Main feeder
breaker
Stand-by
feeder breaker
Main feeder
breaker open
command
Stand-by
feeder close
command
CB close
delay
Figure 944: Signal diagram of 1
st
phase transfer
1MRS759142 F
Control functions
REX640
Technical Manual
1777
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......