Parameter
Values (Range)
Unit
Step
Default
Description
Reclaim time
100...1800000
ms
100
10000
Reclaim time
Terminal priority
1=None
2=Low (follower)
3=High (master)
1=None
Terminal priority
Synchronisation set 0...127
1
0
Selection for syn-
chronizing require-
ment for reclosing
Auto initiation cnd
1=Not allowed
2=When sync fails
3=CB doesn't close
4=Both
2=When sync fails
Auto initiation con-
dition
Tripping line
0...63
1
0
Tripping line,
defines INIT in-
puts which cause
OPEN_CB activa-
tion
Fourth delay in
SOTF
0=False
1=True
0=False
Sets 4th delay into
use for all DEL_IN-
IT signals during
SOTF
First reclose time
0...300000
ms
10
5000
Dead time for CBB1
Second reclose
time
0...300000
ms
10
5000
Dead time for CBB2
Third reclose time
0...300000
ms
10
5000
Dead time for CBB3
Fourth reclose time 0...300000
ms
10
5000
Dead time for CBB4
Fifth reclose time
0...300000
ms
10
5000
Dead time for CBB5
Sixth reclose time
0...300000
ms
10
5000
Dead time for CBB6
Seventh reclose
time
0...300000
ms
10
5000
Dead time for CBB7
Init signals CBB1
0...63
1
0
Initiation lines for
CBB1
Init signals CBB2
0...63
1
0
Initiation lines for
CBB2
Init signals CBB3
0...63
1
0
Initiation lines for
CBB3
Init signals CBB4
0...63
1
0
Initiation lines for
CBB4
Init signals CBB5
0...63
1
0
Initiation lines for
CBB5
Init signals CBB6
0...63
1
0
Initiation lines for
CBB6
Init signals CBB7
0...63
1
0
Initiation lines for
CBB7
Shot number CBB1 0...5
1
0
Shot number for
CBB1
Shot number CBB2 0...5
1
0
Shot number for
CBB2
Shot number CBB3 0...5
1
0
Shot number for
CBB3
Shot number CBB4 0...5
1
0
Shot number for
CBB4
Shot number CBB5 0...5
1
0
Shot number for
CBB5
Shot number CBB6 0...5
1
0
Shot number for
CBB6
Shot number CBB7 0...5
1
0
Shot number for
CBB7
Frq Op counter lim-
it
0...250
1
0
Frequent operation
counter lockout
limit
Table continues on the next page
1MRS759142 F
Control functions
REX640
Technical Manual
1691
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......