4.1.4.5
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "on" and "off".
The operation of GAEPVOC can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
Level
detector
ARMED
I3P
I_A
I_B
I_C
U3P
U_AB
U_BC
U_CA
BLOCK
Arming
check
OPERATE
START
Timer
t
Figure 225: Functional module diagram
Arming check
The fundamental frequency component of the three measured phase-to-phase
generator side voltages are compared with setting
Arm set voltage. If all measured
voltages are below the set
Arm set voltage for longer than Arm delay time, the
ARMED
signal is set to TRUE and simultaneously Level detector is enabled.
The value of
Arm set voltage must be set lower than any emergency low voltage
condition that can occur when the system is under extreme stress conditions. When
the generator returns to service and the voltage exceeds the
Disarm set voltage
setting, the scheme is automatically removed from service (Level detector disabled)
after a time delay (
Disarm delay time setting) and the
ARMED
output is set to FALSE.
GAEPVOC must only be activated when the generator is out-of-service and disabled
when the generator is online.
The setting value of
Arm set voltage should be less than the setting value
of
Disarm set voltage.
Activation of
BLOCK
input resets the
ARMED
output to FALSE state.
Level detector
The measured peak-to-peak values of three phase currents are compared with the
set
Start value. If the measured values exceed Start value, an enable signal is sent to
Timer.
Timer
Once activated, Timer activates the
START
output. The time characteristic is
according to DT. When the operation timer has reached the value set by
Operate
delay time, the
OPERATE
output is activated. If a drop-off situation occurs, the Timer
reset state is activated. If the reset timer reaches the value set by
Reset delay time,
Timer resets.
Protection functions
1MRS759142 F
380
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......