Z1 angle zone x (x = 1...5)
•
Factor K0 zone x (x = 1...5)
•
Factor K0 angle Zn x (x = 1...5)
The reach magnitude and angle are:
(Equation 270)
Angle
angle Z
Z K
N
=
+
(
)
1
1
(Equation 271)
Z
Z zone x
Z angle zone x
j
Z angle zone x
1
1
1
1
=
+
(cos(
)
sin(
))
K
Factor K zone x
Factor K angle znx
j
Factor K angle z
N
=
+
0
0
0
(cos(
)
sin(
n
nx
))
In case of non-directional characteristics, the reactive reach in reverse direction is
defined with the
Z1 reverse zone x (x = 1...5) setting.
(Equation 272)
The total reactive reach in reverse direction includes a part which is defined by the
residual compensation factor K
N
. The characteristic line angle, denoted as α, is the
same for forward and reverse direction.
X
R
Forward
X
R
Reverse
X
R
Non-directional
α
α
α
α
Figure 546: Settings which define the line reach for phase-to-earth impedance
measuring elements if Impedance mode Zn = "Polar"
Protection zone characteristics
DSTPDIS has both “Quadrilateral” and “Mho (circular)” characteristics available for
the protection zones and they can be combined also with the bullet characteristic.
The shape of a tripping characteristic can be set independently for phase-to-earth,
phase-to-phase or three-phase impedance elements. The zone shape is defined
with the
Impedance Chr Gnd Zn setting for phase-to-earth impedance elements,
and with the
Impedance Chr PP Zn setting for phase-to-phase or three-phase
impedance elements. The alternatives are "Quadrilateral", "Mho (circular)", "Mho Dir
line", "Offset Dir line" and "Bullet (combi)".
Protection functions
1MRS759142 F
972
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......