Table 852: Special conditions
Condition
Description
U3P connected to real measurements
The function requires that at least two volt-
age channels are connected as the the third
channel can then be derived. However, it is
recommended that all three voltage channels
are connected.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.5.8.5
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of LVRTPTUV is described using a module diagram. All modules in the
diagram are explained in the next sections.
BLOCK
U3P
OPERATE
START
LVRT
curve
monitoring
U_AB
U_BC
U_CA
U_1
Figure 503: Functional module diagram
LVRT curve monitoring
LVRT curve monitoring starts with detection of undervoltage. Undervoltage
detection depends on
Voltage selection setting. All selectable options are based
on fundamental frequency components.
Function uses phase-to-earth voltages when
Voltage selection is set to “Highest
Ph-to-E” or “Lowest Ph-to-E” and phase-to-phase voltages when
Voltage selection is
set to “Highest Ph-to-Ph” or “Lowest Ph-to-Ph”.
When the
Voltage selection setting is set to “Highest Ph-to-E”, “Lowest Ph-to-E”,
“Highest Ph-to-Ph” or “Lowest Ph-to-Ph”, the measured three-phase voltages are
compared phase-wise to the set
Voltage start value. If the measured value is lower
than the set
Voltage start value setting in number of phases equal to that set Num
of start phases, the
START
output is activated.
The setting options available for
Num of start phases are “Exactly 1 of 3”, "Exactly
2 of 3", and “Exactly 3 of 3”, which are different from conventional setting options
available in other functions. For example,
Num of start phases is set to "Exactly 2 of
3", any two voltages should drop below
Voltage start value within one cycle network
for the
START
output to activate. Even if more than two voltages drop below
Voltage
start value,
START
output is not activated.
1MRS759142 F
Protection functions
REX640
Technical Manual
901
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......