Parameter
Values (Range)
Unit
Step
Default
Description
3=Reverse
Voltage start value 0.01...1.00
xUn
0.01
0.10
Voltage start value
Operate delay time 60...1200000
ms
10
500
Operate delay time
Table 620: MFADPSDE Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Operating quantity 1=Adaptive
2=Amplitude
3=Resistive
1=Adaptive
Operating quantity
selection
Min operate current 0.005...5.000
xIn
0.001
0.010
Minimum operate
current
Tilt angle
2.0...20.0
deg
0.1
5.0
Characteristic tilt
angle
Table 621: MFADPSDE Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Operation mode
1=Intermittent EF
2=Transient EF
3=General EF
4=Alarming EF
3=General EF
Operation criteria
Table 622: MFADPSDE Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Peak counter limit
2...20
1
2
Peak counter limit
for restriking EF
Start delay time
30...60000
ms
1
30
Start delay time
Reset delay time
0...60000
ms
1
500
Reset delay time
Pol reversal
0=False
1=True
0=False
Rotate polarizing
quantity
4.2.9.9
MFADPSDE Monitored data
Table 623: MFADPSDE Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
ANGLE
FLOAT32
-180.00...180.00
deg
Angle between polar-
izing and operating
quantity
I_OPER
FLOAT32
0.000...40.000
xIn
Calculated operating
current
MFADPSDE
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS759142 F
Protection functions
REX640
Technical Manual
581
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......