Characteristic
Value
Start time
Typically <55 ms
Reset time
<40 ms
Reset ratio
Typically 1.04
Retardation time
<35 ms
Operate time accuracy in definite time mode mode ±1.0% of the set value or ±20 ms
4.1.10
Thermal overload protection for motors MPTTR (ANSI
49M)
4.1.10.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Thermal overload protection for
motors
MPTTR
3Ith>M
49M
4.1.10.2
Function block
Figure 237: Function block
4.1.10.3
Functionality
The thermal overload protection for motors function MPTTR protects the electric
motors from overheating. MPTTR models the thermal behavior of motor on the
basis of the measured load current and disconnects the motor when the thermal
content reaches 100 percent. The thermal overload conditions are the most often
encountered abnormal conditions in industrial motor applications. The thermal
overload conditions are typically the result of an abnormal rise in the motor running
current, which produces an increase in the thermal dissipation of the motor and
temperature or reduces cooling. MPTTR prevents an electric motor from drawing
excessive current and overheating, which causes the premature insulation failures of
the windings and, in worst cases, burning out of the motors.
4.1.10.4
Analog channel configuration
MPTTR has one analog group input which must be properly configured.
Table 475: Analog inputs
Input
Description
I3P
Three-phase currents
Protection functions
1MRS759142 F
410
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......