• Area B defines the linear growth recovery voltage level from
Voltage level 1 to
Voltage level 2 in a time period from Recovery time 1 to Recovery time 2.
• Area C is the zone where voltage stabilizes.
Voltage level 3 is defined to same
value as
Voltage level 2. The system should remain above this voltage in a time
period from
Recovery time 2 to Recovery time 3.
The system restores to a normal state and function resets when the voltage is equal
or greater than
Voltage level 4 after Recovery time 4 time period.
When the voltage at the point of common coupling is above the LVRT curve, the
generation unit must remain connected, and must be disconnected only if the
voltage takes values below the curve.
Figure 507: A typical required ride-through voltage capability of generating unit
The LVRT requirement depends on the power system characteristics and the
protection employed, varying significantly from each other. The requirement also
differs from country to country. LVRTPTUV function incorporates four types of LVRT
curves which satisfy most of the power system needs. Grid operators can fine-tune
the LVRT curve by setting the parameters as per their requirement, making the
use simpler in comparison with different conventional undervoltage protection with
different operate time setting and logics.
4.5.8.7
Signals
LVRTPTUV Input signals
Table 854: LVRTPTUV Input signals
Name
Type
Default
Description
U3P
SIGNAL
-
Three-phase voltages
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
1MRS759142 F
Protection functions
REX640
Technical Manual
905
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......