R
SI
is the initial stator resistance calculated from line voltages and
phase currents,
R
N
is the rotor resistance at nominal speed and
R
L
is the rotor resistance at locked rotor.
The rotor positive and negative sequence resistance vary depending on the motor
slip. The slip estimate values are used to calculate the rotor positive and negative
sequence resistance factors:
=
(
)
(Equation 51)
=
(
)∙(
)
(Equation 52)
R
r+
is the rotor positive sequence resistance factor,
R
r-
is the rotor negative sequence resistance factor,
R
L
is the rotor resistance at locked rotor,
R
N
is the rotor resistance at nominal speed and
S
is the motor slip.
These resistance factors are then used in the thermal calculations to depict the
thermal behavior that the skin effect causes.
The skin effect describes the situation where the rotor bars are induced with high
amplitude and high frequency current which make the current flow in the rotor bars
to be distributed close to the rotor bar surface, increasing the resistance of the
rotor bar.
The rotor resistances depend on the relation of the rotating magnetic fluxes and the
rotor speed, i.e. slip. The faster the fluxes cut the rotor bars the higher amplitude
and higher frequency currents are induced to the rotor bars.
The rotor positive sequence resistance factor R
r+
is at its highest at motor standstill
(S=1), and smallest when the slip is at nominal value (S≈0). The rotor negative
sequence resistance factor R
r-
, however, grows larger as the rotor starts to revolve in
the intended direction since the magnetic flux that the unbalance creates rotates in
the opposite direction compared to the rotor, making the skin effect stronger.
STALL_IND
output is provided for monitoring purposes or external logic. A TRUE
value indicates that the rotor is stalling. The output is functional only when the
motor is energized.
The rotational speed of the rotor is provided in monitored data at SPEED_RPM. The
monitored data is also only functional when the motor is energized.
4.1.11.6
Application
Rotor thermal overload protection function is intended to prevent the rotor from
overheating especially during motor starting and abnormal operating conditions
1MRS759142 F
Protection functions
REX640
Technical Manual
429
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......