4.8.2.2
Function block
Figure 592: Function block
4.8.2.3
Functionality
The reverse power/directional overpower protection function DOPPDPR can be
used for generator protection against delivering an excessive power beyond the
generator's capacity to the grid, against the generator running like a motor, and
against the motor running like a generator and for protecting a motor which
consumes more reactive power due to loss of field. It can also be used in feeder
protection for indicating overload on the distribution system, to indicate that a
customer is supplying power into the grid and for protecting the transformer from
delivering an excessive load.
The function starts and operates when the measured power exceeds the set limit
and in a specified direction. The operate time characteristics are according to
definite time (DT).
This function contains a blocking functionality. It is possible to block the function
outputs, timer or the function itself.
4.8.2.4
Analog channel configuration
DOPPDPR has two analog group inputs which must be properly configured.
Table 999: Analog inputs
Input
Description
I3P
Three-phase currents
U3P
Three-phase voltages
See the preprocessing function blocks in this document for the possible
signal sources.
There are a few special conditions which must be noted with the configuration.
Table 1000: Special conditions
Condition
Description
U3P connected to real meas-
urements
The function can work with the corresponding one volt-
age channel connected if the
Measurement mode
is set to
"PhsAB", "PhsBC", "PhsCA", "PhsA", "PhsB" or "PhsC".
The function requires that at least two (the third voltage will
be derived) or all three voltage channels are connected for
the other measurement modes.
1MRS759142 F
Protection functions
REX640
Technical Manual
1063
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......