• The “Vol Dep Overcur” method combines overcurrent and undervoltage
conditions. An undervoltage condition allows lower current threshold settings
and increases the sensitivity of the fault detection.
• The “Under impedance” method uses fault loop impedance for identifying the
faulted phases. The underimpedance characteristic can be either quadrilateral
or circular in shape. The sensitivity of the fault detection is defined by an
independent setting in resistive and reactive reaches. The underimpedance
method is supervised by a load encroachment logic which ensures that the load
impedance does not interfere with the faulted phase selection.
The ”OC AND Und impedance” method combines “Overcurrent” and “Under
impedance” methods so that both criteria have to be fulfilled.
All phase selection methods require that all three phase currents are measured
and all three phase-to-earth voltages are available. If only phase-to-phase voltages
are available (
Phase voltage Meas = “Ph-to-ph without Uo”), only phase-to-phase
measuring loops can be released for measurement. The release of phase-to-earth
fault measuring elements is then blocked,
RELEASE_PE
= “No fault”.
The operation of the faulted phase selection function is highly dependent on the
earth-fault detection function. The phase preference or faulted loop selection logic
can be set to filter the faulted phases to be released for measurement in the
protection zones.
The general indication of a fault is given in the binary output
START_GFC
. The
faulted phase information can be found from the integer monitored data signal
STARTS_GFC
.
Table 909: Enumeration values for integer monitored data signal STARTS_GFC
Enumeration name
Value
No fault
-5
AG Fault
1
BG Fault
2
CG Fault
3
AB Fault
4
BC Fault
5
CA Fault
6
ABC Fault
7
The fault loops released for measurement are indicated with the integer monitored
data signals
RELEASE_PE
and
RELEASE_PP
. These signals may be filtered by the
phase preference of the faulted loop selection logic.
Table 910: Enumeration values for integer monitored data signal RELEASE_PE
Enumeration name
Value
No fault
-5
AG Fault
1
BG Fault
2
CG Fault
3
AB Fault
4
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
949
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......