The current measurement of the function is based on two alternative measurement
modes, "DFT" and "Peak-To-Peak". The measurement mode is selected using the
Measurement mode setting.
If the current magnitude is below 0.02 · I
N
, where I
N
is the nominal phase current,
the impedance value is not evaluated and the maximum impedance value (99.999
pu) is shown in the Monitored data view.
The calculated impedances are converted to a pu impedance as the
operating characteristics are defined using the
Polar reach setting in
%Zb.
The calculated phase-phase impedance amplitudes Z_AMPL_AB, Z_AMPL_BC and
Z_AMPL_CA are available as pu values in the Monitored data view.
Underimpedance detection
The operating characteristic is an origin-centric circle on the impedance plane. The
origin-centric circular characteristic is defined using the
Polar reach setting. If the
calculated impedance value enters the circle in the impedance plane, the module
sends an enabling signal to start the Timer.
Figure 571: Origin-centric circular operating characteristics
Separate zones with an offset-mho characteristic can be designed using multiple
instances of the UZPDIS function with
Offset enable setting and parameterized
with
Offset and Displacement setting values as shown in Figure
Offset is
the distance of the top of the circle from R-axis. If the sign of the
Offset is positive,
the top of the circle is above the R-axis and if it is negative, the top of the circle
will be below the R-axis.
Displacement is the distance by which the center of the
circle is displaced from the X-axis. If the sign of the
Displacement setting is positive,
1MRS759142 F
Protection functions
REX640
Technical Manual
1029
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......