4.2.8.6
Application
Mechanical and thermal stress deteriorates stator winding insulation, which can
eventually cause an earth fault between the winding and stator core.
The fault current magnitude in case of stator earth fault depends on the grounding
type. Common practice in most countries is to earth the generator neutral side
through a resistor. The resistor is selected such as to limit the maximum earth-fault
current in the range of 5...10 A. The same can be done by connecting a single phase
voltage transformer between the neutral side and earth, and with an equivalent
resistor on the secondary side of the transformer.
In a normal operating condition, that is, when there is no earth fault, the residual
voltage is close to zero with no zero-sequence current flowing in the generator.
When a phase-to-earth fault occurs, the residual voltage increases and the current
flows through the neutral. The simplest way to protect the stator winding against
an earth fault is by providing residual overvoltage protection (or residual/neutral
overcurrent protection). However, at best these simple schemes can protect only
95% of the stator winding, leaving 5% of the neutral end unprotected. This is
because the voltage generated in the faulted winding decreases as the fault point
becomes closer to the neutral point and it is not enough to drive the protection.
Under certain unfavorable conditions, the blind zone may extend up to 20% from the
neutral point.
An earth fault close to the neutral point is not dangerous, but an undetected fault
may develop into an interturn fault or phase-to-phase fault. Also an undetected
earth fault near the neutral point is bypassing the high-impedance grounding, and
then another earth fault at the terminal results in a catastrophic situation.
Therefore, it is important to extend the protection to full 100%. The third harmonic
voltage-based protection is one such protection which provides effective protection
during an earth fault at the neutral point, and at least in the range up to 15...20%
from the neutral point along the stator winding.
To achieve a complete stator earth-fault protection, two protection functions
should always run in parallel.
• Fundamental frequency-based residual overvoltage protection ROVPTOV
• Third harmonic-based stator earth-fault protection H3EFPSEF
Figure 314: Complete stator earth-fault protection
Protection functions
1MRS759142 F
546
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......