4.5.7.2
Function block
Figure 494: Function block
4.5.7.3
Functionality
The overexcitation protection function OEPVPH is used to protect generators
and power transformers against an excessive flux density and saturation of the
magnetic core.
The function calculates the U/f ratio (volts/hertz) proportional to the excitation
level of the generator or transformer and compares this value to the setting limit.
The function starts when the excitation level exceeds the set limit and operates
when the set operating time has elapsed. The operating time characteristic can be
selected to be either definite time (DT) or overexcitation inverse definite minimum
time (overexcitation type IDMT).
This function contains a blocking functionality. It is possible to block the function
outputs, reset timer or the function itself.
4.5.7.4
Analog channel configuration
OEPVPH has two analog group inputs which must be properly configured.
Table 840: Analog inputs
Input
Description
I3P
Three-phase currents
U3P
Three-phase voltages
See the preprocessing function blocks in this document for the possible
signal sources.
There are a few special conditions which must be noted with the configuration.
Table 841: Special conditions
Condition
Description
U3P connected to real measurements
The function can work with at least one volt-
age channel connected (A, B or C according
to
Phase selection
“1”, “2” or “3”) if
Voltage
selection
is set to "phase-to-earth".
The function can work with any two voltage
channels connected (AB, BC or CA according
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
885
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......