
can be more severe than the heating effects and therefore a separate unbalance
protection is used.
Unbalances in other connected loads in the same busbar can also affect the motor.
A voltage unbalance typically produces 5 to 7 times higher current unbalance.
Because the thermal overload protection is based on the highest TRMS value of
the phase current, the additional heating in stator winding is automatically taken
into account. For more accurate thermal modeling, the
Negative Seq factor setting
is used for taking account of the rotor heating effect.
Negative Seq factor
R
R
R
R
=
2
1
(Equation 41)
R
R2
Rotor negative sequence resistance
R
R1
Rotor positive sequence resistance
A conservative estimate for the setting can be calculated:
Negative Seq factor
I
LR
=
175
2
(Equation 42)
I
LR
Locked rotor current (multiple of set
Rated current
). The same as the start-up
current at the beginning of the motor start-up.
For example, if the rated current of a motor is 230 A, start-up current is 5.7 x I
r
,
Negative Seq factor
=
=
175
5 7
5 4
2
.
.
(Equation 43)
Setting the thermal restart level
The restart disable level can be calculated as follows:
θ
i
startup time of the motor
operate time when no prior load
=
−
×
100
10
%
0
0%
+
margin
(Equation 44)
For example, the motor start-up time is 11 seconds, start-up current 6 x rated and
Time constant start is set for 800 seconds. Using the trip curve with no prior load,
the operation time at 6 x rated current is 25 seconds, one motor start-up uses 11/25
≈ 45 percent of the thermal capacity of the motor. Therefore, the restart disable
level must be set to below 100 percent - 45 percent = 55 percent, for example to 50
percent (100 percent - (45 p margin), where margin is 5 percent).
Setting the thermal alarm level
Tripping due to high overload is avoided by reducing the load of the motor on a
prior alarm.
Protection functions
1MRS759142 F
420
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......