A fault in the voltage-measuring circuit is called a fuse failure. This term is
misleading since a blown fuse is just one of the many possible reasons for a broken
circuit. Since incorrectly measured voltage can result in a faulty operation of some
of the protection functions, it is important to detect the fuse failures. A fast fuse
failure detection is one of the means to block voltage-based functions before they
operate.
Three phase network
VT
Fault in a measuring
circuit between
voltage transformer
and protection relay
e.g. blown fuse
REF 615
Figure 759: Fault in a circuit from the voltage transformer to the protection relay
A fuse failure occurs due to blown fuses, broken wires or intended substation
operations. The negative sequence component-based function can be used to
detect different types of single-phase or two-phase fuse failures. However, at
least one of the three circuits from the voltage transformers must be intact. The
supporting delta-based function can also detect a fuse failure due to three-phase
interruptions.
In the negative sequence component-based part of the function, a fuse failure is
detected by comparing the calculated value of the negative sequence component
voltage to the negative sequence component current. The sequence entities are
calculated from the measured current and voltage data for all three phases. The
purpose of this function is to block voltage-dependent functions when a fuse
failure is detected. Since the voltage dependence differs between these functions,
SEQSPVC has two outputs for this purpose.
6.5.7
Signals
6.5.7.1
SEQSPVC Input signals
Table 1276: SEQSPVC Input signals
Name
Type
Default
Description
I3P
SIGNAL
-
Three-phase currents
U3P
SIGNAL
-
Three-phase voltages
BLOCK
BOOLEAN
0=False
Block of function
Table continues on the next page
Supervision functions
1MRS759142 F
1336
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......