(Equation 262)
(Equation 263)
The phase-to-phase measuring elements are based on the formula:
(Equation 264)
(Equation 265)
(Equation 266)
The faulted phase identification is done by comparing the measured impedance to
the operating characteristics in the impedance domain. If a measured fault loop
impedance is inside the characteristics, the corresponding phases are identified as
faulty.
The shape of the characteristic is selected with the
Z Chr Mod Ph Sel GFC setting.
Two shapes are available.
• "Mho (circular)", Non-directional mho
• "Quadrilateral", Non-directional quadrilateral
The two shapes can be flexibly configured. It is possible to set the reactive reaches
independently in forward and in reverse direction and for phase-to-earth (Gnd) and
phase-to-phase (PP) measurement elements, for example, the
X Gnd Fwd reach GFC,
X Gnd Rv reach GFC, X PP Fwd reach GFC and X PP Rv reach GFC settings. Also,
the resistive reach in case of quadrilateral characteristic can be set both forward
and reverse independently of reactive reaches, for example, the
Ris Gnd Fwd Rch
GFC, Ris Gnd Rv Rch GFC, Ris PP Fwd Rch GFC and Ris PP Rv Rch GFC settings. The
characteristic is always mirror-symmetric around the reactance axis.
The impedance settings are in primary ohms.
In case of heavy loaded feeders, the optional load encroachment logic can be
enabled with the
Load Dsr mode GFC setting. The logic reserves an area for load
Protection functions
1MRS759142 F
954
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......