earthing Ris in primary ohms i.e. the maximum earthing resistance encountered in
protected feeder.
Fault duration t
f
[sec.]
Permissible touch voltage, U
Tp
converted into
corresponding permissible fault current, I
Fp
[A]
0.05
702 V/R
Emax
0.10
496 V/R
Emax
0.20
351 V/R
Emax
0.50
222 V/R
Emax
1.00
157 V/R
Emax
2.00
111 V/R
Emax
5.00
70 V/R
Emax
10.00
50 V/R
Emax
In some countries, safety during an earth fault is defined in terms of highest
allowed earth potential rise (EPR) as a function of fault duration. As an example,
in Finnish national Electrical Safety Regulations 89 define highest allowed earth
potential rise as a function of fault duration as shown in table below.
Table 630: Highest allowed EPR values based on Electrical Safety
Group
Highest allowed EPR [V], when earth fault is automatically
disconnected within time
t
[sec]
a
750V/√
t
b
2000V/√
t
c
3000V/√
t
d
500V/√
t
e1
750V/√
t
e2
1000V/√
t
The regulations of
are implemented into IFPTOC. In case
Operation
principle = “EF current based”, setting Maximum earthing Ris is used to convert
the highest allowed earth potential risevalues into corresponding earth-fault current
values. Setting
IEEE multiplier is set to equal the highest allowed voltage value,
for example for group d,
IEEE multiplier = 500. Conversion of the highest allowed
earth potential rise value to the highest allowed earth-fault current magnitude with
setting
Maximum earthing Ris is shown in
.
Setting
Maximum earthing Ris in primary ohms is selected based on the maximum
earthing resistance encountered in protected feeder.
Table 631: Conversion of the highest allowed earth potential rise value into corre-
sponding earth-fault current values according to the Electrical Safety Regulations
1MRS759142 F
Protection functions
REX640
Technical Manual
609
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......